Power Cable Screened (NYCY)

Insulation

PVC

Sheath

PVC

Standard

IEC 60502-1

Nominal voltage

0.6-1 KV

Conductor

1.2

Application

This type of cable to distribution boards, power plants, electric meters, and lighting homes and streets as well as control cables for the transmission of control impulses and test data. And in general where electrical and mechanical protection is needed to be used. These cables can be used in outdoor, soil, indoor, and cable channels. Concentric conductor can be neutrialized at the Same time as a shiled, wire or earthed used.

Cross SectionNo. Dia StrandsInsulation ThicknessSheath ThicknessMean Overall diaMax , T=20c ResistanceCurrent CapacityAPP. Weight
(mm۲)(mm)(mm)(mm)(mm)(Ω/km)Amp/T=25oC(kg/km)
1×1.15/1.151×1.38+12×0.401.01.87.512.11980
1×2.5/2.51×1.78+12×0.521.01.88.07.4127104
1×4/41×2.25+19×0.521.01.89.04.6138146
1×6/61×2.78+12×0.811.01.810.03.0847192
1×10/101×3.57+19×0.811.01.811.01.8364273
1×16/167×1.72+16×1.131.01.813.01.1586411
1×25/257×2.14+25×1.131.21.815.00.727110615
1×35/357×2.52+35×1.131.21.816.00.524140810
2×1.5/1.51×1.38+12×0.401.01.811.712.118205
2×2.5/2.51×1.78+12×0.521.01.813.27.4125250
2×4/41×2.25+19×0.521.01.815.74.6137341
2×6/61×2.78+12×0.811.01.816.23.0843423
2×10/101×3.57+19×0.811.01.8181.8360585
2×16/167×1.72+16×1.131.01.8221.1582864
2×25/257×2.14+25×1.131.21.826.10.7271041173
2×35/357×2.52+35×1.131.21.8280.5241331450
3×1.5/1.51×1.38+12×0.401.01.815.012.117225
3×2.5/2.51×1.78+12×0.521.01.816.07.4123288
3×4/41×2.25+19×0.521.01.818.04.6135402
3×6/61×2.78+12×0.811.01.819.03.0840512
3×10/101×3.57+19×0.811.01.821.01.8356713
3×16/167×1.72+16×1.131.01.823.01.15771066
3×25/257×2.14+25×1.131.21.828.00.727981570
3×35/357×2.52+35×1.131.21.830.00.5241262042